Table 310.16 · 240.6(A)

What Size Wire for a 90 Amp Breaker?

Verified against NEC 2023, checked against the 2026 edition · Last checked August 18, 2026

A 90 amp breaker takes 3 AWG copper or 2 AWG aluminum with 75°C terminations, sized from NEC Table 310.16. This assumes THHN-class conductors in conduit, no more than three current-carrying conductors, 86°F ambient and a non-continuous load. With 60°C terminations or NM-B cable, use 2 AWG copper · 110.14(C)(1)(a), 334.80.

Common on this rating: large tankless water heaters.

Minimum conductor sizes for a 90 A breaker. THHN-class insulation in raceway, 3 or fewer current-carrying conductors, 86°F ambient, non-continuous load. Same values in NEC 2023 and 2026.
ConductorSizeUsableBasis
Copper · 75°C terminals3 AWG100 ATable 310.16 · 75°C column
Aluminum · 75°C terminals2 AWG90 ATable 310.16 · 75°C column
Copper · 60°C terminals or NM-B2 AWG95 ATable 310.16 · 60°C column · 110.14(C)(1)(a), 334.80
Aluminum · 60°C terminals1/0 AWG100 ATable 310.16 · 60°C column · 110.14(C)(1)(a)
Ground wire (EGC)8 AWG Cu or 6 AWG AlTable 250.122

EGC from Table 250.122. If conductors are upsized for voltage drop, the EGC upsizes in proportion · 250.122(B).

What changes this answer

  • Continuous load · 210.19(A)

    A load running 3 hours or more needs conductors sized at 125% of that current. Sizes above assume a non-continuous load.

  • More than 3 conductors · 310.15(C)(1)

    Four or more current-carrying conductors in one raceway derate ampacity by 20% or more. Run the calculator with your count.

  • Hot locations · 310.15(B)(1)

    Ambient above 86°F cuts ampacity. Attics and rooftop conduit routinely trigger this correction.

  • Long runs and voltage drop

    Distance does not change the NEC minimum, but past roughly 100 feet voltage drop usually forces a larger conductor.

  • Round-up rule · 240.4(B)

    Where a conductor ampacity is not a standard breaker rating, the next higher standard breaker is sometimes permitted. The table above never relies on it, so its sizes never depend on that permission.

Check your exact conditions

The calculator below starts at 90 A. Set your ambient, conductor count and continuous load, and it re-sizes the wire with every step cited.

LoadA
Continuous load
Wiring
Material
Insulation
NEC edition
Ambient temperature°F
Current-carrying conductors
TerminalsAuto follows 110.14(C): 60°C column up to 100 A, 75°C above.
Result
3 AWGCu·90°C
Passes NEC 2023 · Table 310.16
Ampacity115 A
After derating115 A
Terminal limit100 A
How this was determined
Base ampacity · 90°C column · Table 310.16115 A
Ambient 86°F · 310.15(B)(1)× 1.00
3 conductors · 310.15(C)(1)× 1.00
After derating115 A
Terminal limit · 75°C · 110.14(C)100 A
Limited by terminal rating · 110.14(C)100 A
Table 310.16 · Copper · NEC 2023
NEC 2023 Table 310.16, allowable ampacities in amperes for copper conductors rated 60°C, 75°C and 90°C, not more than three current-carrying conductors in a raceway, 30°C (86°F) ambient temperature
SIZE60°C75°C90°C
14 AWG152025
12 AWG202530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
3 AWG85100115
2 AWG95115130
1 AWG110130145
1/0 AWG125150170
2/0 AWG145175195
3/0 AWG165200225
4/0 AWG195230260
250 kcmil215255290
300 kcmil240285320
350 kcmil260310350
400 kcmil280335380
500 kcmil320380430
600 kcmil350420475
700 kcmil385460520
750 kcmil400475535
1000 kcmil455545615

Ampacities from NEC 2023 Table 310.16, 30°C ambient basis. Highlighted: your conductor size and insulation column.

Size it on the job site, offline.

The JobVolt app runs this same verified math with no signal, keeps every calculation in History, and turns it into an inspector-ready PDF submittal on your letterhead.

Download on the App StoreGet it on Google Play

Common questions

What size wire do I need for a 90 amp breaker?
3 AWG copper or 2 AWG aluminum with 75°C terminations, per NEC Table 310.16. In NM-B cable or on 60°C terminals, 2 AWG copper.
Does NM-B cable change the wire size for 90 amps?
Yes. NM-B cable is sized from the 60°C column · 334.80, so the answer becomes 2 AWG copper instead of 3 AWG.
Can I use aluminum wire on a 90 amp breaker?
Yes. 2 AWG aluminum at 75°C terminations carries 90 A, which covers a 90 A breaker · Table 310.16. Modern aluminum conductors are AA-8000 alloy, not the old 1960s wire.
Does distance change the wire size for 90 amps?
Not in Table 310.16, but long runs lose voltage. Size the run with JobVolt's free voltage drop calculator so the equipment still sees full voltage.