JobVolt
Table 250.122

What Size Ground Wire for a 45 Amp Breaker?

Verified against NEC 2023, checked against the 2026 edition · Last checked August 18, 2026

A 45 amp breaker or feeder needs an equipment grounding conductor of 10 AWG copper or 8 AWG aluminum · Table 250.122.

Common on this rating: HVAC equipment with a marked maximum breaker. Run with 8 AWG copper circuit conductors, the ground is 10 AWG copper.

Two different tables answer this question. A breaker, circuit or sub panel takes an equipment grounding conductor from Table 250.122, entered with the breaker rating. A service takes a grounding electrode conductor from Table 250.66, entered with the service conductor size. Mixing them up can change the answer by a size or more.

Equipment grounding conductor for a 45 A breaker, circuit or sub panel feeder. Same values in NEC 2023 and 2026.
ConductorSizeBasis
Copper EGC10 AWGTable 250.122
Aluminum EGC8 AWGTable 250.122

The EGC never needs to be larger than the circuit conductors · 250.122(A). Upsized circuit conductors mean a proportionally upsized EGC · 250.122(B). Parallel runs in separate raceways carry a full-size EGC in each raceway · 250.122(F).

Grounding sized in seconds, offline.

The JobVolt app sizes EGC and GEC with the exact table row cited, handles upsizing for voltage drop, and exports inspector-ready PDF submittals.

Download on the App StoreGet it on Google Play

Common questions

What size ground wire for a 45 amp breaker?
An equipment grounding conductor of 10 AWG copper or 8 AWG aluminum, from Table 250.122. The EGC never needs to be larger than the circuit conductors · 250.122(A).
What size ground wire for a 45 amp sub panel?
The same as the breaker answer: 10 AWG copper or 8 AWG aluminum, sized by the 45 A feeder breaker per Table 250.122.
Is the ground wire the same as the neutral?
No. The grounded service conductor, the neutral, is a current-carrying conductor sized by 250.24(C) and 220.61. It is not the EGC of Table 250.122 and not the GEC of Table 250.66.
What if my circuit conductors were upsized for voltage drop?
If the circuit conductors were upsized for voltage drop, the EGC must be upsized in the same ratio of circular-mil area · 250.122(B).