JobVolt
Table 310.16

How Many Amps Can 1000 kcmil Copper Wire Handle?

Verified against NEC 2023, checked against the 2026 edition · Last checked August 19, 2026

1000 kcmil copper wire carries 455 A at 60°C, 545 A at 75°C and 615 A at 90°C · Table 310.16. Which column applies depends on the termination rating · 110.14(C).

Common landing spot: a 500 A breaker or feeder.

1000 kcmil copper allowable ampacity by termination column. Not more than three current-carrying conductors, 86°F ambient. Same values in NEC 2023 and 2026.
Column · insulation examplesAmpacityBasis
60°C · TW, UF455 ATable 310.16
75°C · THW, THWN, XHHW wet, USE545 ATable 310.16
90°C · THHN, THWN-2, XHHW-2615 ATable 310.16

THHW and XHHW are 90°C only in dry and damp locations; wet locations put them in the 75°C column. XHHW-2 and THWN-2 hold 90°C wet or dry · Table 310.4(1).

Adjustment factors for more than three current-carrying conductors in one raceway or cable, applied to the 1000 kcmil values above · Table 310.15(C)(1).
Current-carrying conductorsPercent of table ampacity
4 to 680%
7 to 970%
10 to 2050%
21 to 3045%
31 to 4040%
41 and more35%

Ambient above 86°F applies a further correction from the band table of 310.15(B)(1). The free wire size calculator applies both automatically.

Derate it in seconds, offline.

The JobVolt app applies ambient correction, conductor adjustment and termination limits to 1000 kcmil copper with every step cited, then exports inspector-ready PDF submittals.

Download on the App StoreGet it on Google Play

Common questions

How many amps can 1000 kcmil copper wire handle?
455 A at 60°C terminations, 545 A at 75°C and 615 A at 90°C, per NEC Table 310.16 with no more than three current-carrying conductors at 86°F ambient.
What size breaker goes on 1000 kcmil copper?
500 A is the largest standard rating at or under the 75°C ampacity of 545 A · 240.6(A). Because that ampacity is not a standard rating, the next size up is sometimes permitted by 240.4(B) when the load allows.
Does conduit fill change the ampacity of 1000 kcmil copper?
Four or more current-carrying conductors in one raceway derate the table value · 310.15(C)(1). At 4 to 6 conductors, 1000 kcmil copper starts from 80% of the 90°C cell: 492 A before any further correction. Heat above 86°F derates it further · 310.15(B)(1).